enquiries@amacne.com Home Services Air Conditioning Mechanical Electrical Ventilation Planned Maintenance Calculator Work Experience Centre Contact Start Your Project

05 — Planned Maintenance

Planned Maintenance

Scheduled servicing and live compliance reporting, backed by reactive callout cover — so small issues get caught before they become expensive ones.

Start Your Project Email Us

What this covers

Scheduled preventative servicing

Planned visits set around the equipment's actual service requirements and your operating hours.

Compliance reporting

Service records and compliance documentation kept current, so audits don't become a scramble.

Reactive callout

Priority attendance for contract clients when something fails between planned visits.

Flexible contract terms

Contracts scoped to the estate — single site through to multi-site national portfolios.

How often does a system legally need a leak check?

The F-Gas Regulation sets the interval by the refrigerant charge expressed in tonnes of CO₂ equivalent. Same kilograms, different gas, different answer — so it's worked out per unit.

Charge (tCO₂e)Check intervalWith fixed leak detectionR32 charge (GWP 675)R410A charge (GWP 2,088)
Under 5None requiredUnder 7.4 kgUnder 2.4 kg
5 – 50Every 12 monthsEvery 24 months7.4 – 74 kg2.4 – 24 kg
50 – 500Every 6 monthsEvery 12 months74 – 740 kg24 – 239 kg
500 and overEvery 3 monthsEvery 6 months740 kg and over239 kg and over

Why it matters: a typical office cassette on R410A crosses the first threshold at about 2.4 kg, so most commercial systems need at least an annual check. Hermetically sealed systems under 10 tCO₂e and labelled as such are exempt. Thresholds per the GB F-Gas Regulation as retained.

What a service visit typically covers

Indoor unit

Filters cleaned or replaced, evaporator coil inspected, fan checked, condensate tray and pump flushed and the drain proved to discharge.

Outdoor unit

Coil cleaned, fan motor current recorded, contactors and capacitors inspected, mounting and clearances confirmed.

Refrigerant circuit

Operating pressures and temperatures logged, electronic leak detection across the joints, and the F-Gas record updated.

Performance and report

Return and supply air temperatures measured and compared with commissioning figures. A falling ΔT is usually the first sign of a problem nobody has noticed yet. Report issued per unit.

Typical sectors

Retail estates, managed offices, healthcare facilities, schools and multi-site commercial portfolios.

Worth knowing

Maintenance contracts are available on systems AMAC didn't originally install, subject to an initial condition survey.